- PNCR
- SCR
- SNCR
- Semi-dry system
- Dry system
- Photovoltaic
- Case
New energy
AC metal-enclosed switchgear
Position:Home > AC metal-enclosed switchgear >
KYN61-40.5 Armored AC Metal-enclosed Switchgear
KYN61-40.5 armored AC metal-enclosed switchgear is suitable for three-phase AC 50HZ, 40.5KV single-bus sectional power system, mainly used in power station, substation, industrial and mining enterprises and high-rise building Distribute electrical energy and control, protect, and monitor the circuit. Meet the requirements of IEC60298, GB3906, DL404 and other standards, and have a perfect "five anti-function."
The main technical parameters:
The main technical parameters:
Rated insulation voltage | 40.5KV | |||||
Rated frequency | 50HZ | |||||
Main bus rated current | 1250,1600,2000A | |||||
Rated bus current | 630,1250,1600A | |||||
Rated insulation level | Interphase and relatively | One isolation fracture | ||||
1min power frequency withstand voltage (effective value) | 95KV | 115KV | ||||
Lightning impulse withstand voltage (peak) | 185KV | 215KV | ||||
Auxiliary control circuit power frequency withstand voltage | 2000V | |||||
Rated short-circuit breaking current | 25,31.5KA | |||||
Rated short-circuit current (peak) | 63,80KA | |||||
Rated short-term withstand current (4s) | 25,31.5KA | |||||
Rated peak withstand current | 63,80KA | |||||
Control circuit rated voltage | Dc or Ac 110/220v | |||||
Protection level | shell | IP4X | ||||
Circuit breaker room door or compartment | IP2X |